Channel Configurations: Channel Options:
Stainless Steel (Trojan option)
Concrete (by others)
Channel Configurations: Lamp Banks in Series:
Up to 2
Channel Configurations: Level Control Device Options:
Fixed weir
Electrical Requirements: Power Distribution:
Individual GFI Receptacles
Electrical Requirements: Power Distribution Center:
-
Electrical Requirements: Power Input:
120V, single phase
Electrical Requirements: Quantity Required:
1 receptacle per 2 modules
Enclosure Ratings: Ballast Cooling Method:
Convection; no air conditioning or forced air required
Enclosure Ratings: Installation Location:
Indoor or outdoor
Enclosure Ratings: Module Frame/Ballast Enclosure:
TYPE 6P (IP67)
Enclosure Ratings: System Monitor/Control Center:
304 stainless steel
System Characteristics: Ballast Type:
Electronic; non-variable
System Characteristics: Bank Configuration:
Up to 10 modules per bank
System Characteristics: Input Power Per Lamp:
45 or 87.5 Watts
System Characteristics: Lamp Configuration:
Horizontal, parallel to flow
System Characteristics: Lamp Type:
Low-pressure
System Characteristics: Module/Bank Frame:
-
System Characteristics: Module Configuration:
2 or 4 lamps per module
System Characteristics: Typical Applications:
Up to 3 MGD (473 m3/hr)
System Monitoring & Controls: Controller:
Monitoring and bank control
System Monitoring & Controls: Local Status Indication:
• Lamp Age (hours)
• UV Intensity (mW/cm2)
• Bank Status (on/off)
• Low Intensity Alarm
• Lamp Failure Alarm
System Monitoring & Controls: Remote Alarms:
• UV Intensity (4-20 mA)
• Common Alarm (discrete)
System Monitoring & Controls: UV Intensity Monitoring:
Optional